Wuxi Fenigal Science & Technology Co., Ltd.

Wuxi Fenigal Science & Technology Co., Ltd Manufacturer and Supplier for Industrial & Lighting Products

Manufacturer from China
Verified Supplier
6 Years
Home / Products / Industrial Circuit Breaker /

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Contact Now
Wuxi Fenigal Science & Technology Co., Ltd.
Visit Website
City:wuxi
Province/State:jiangsu
Country/Region:china
Contact Person:MrHarry
Contact Now

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Ask Latest Price
Video Channel
Brand Name :Schneider Electric
Model Number :C120
Certification :CCC, CE, GS etc.
Place of Origin :China
MOQ :12pcs / 1doz.
Price :USD1~15/unit
Payment Terms :T/T, Western Union
Supply Ability :100,000 pcs/month
Delivery Time :2~15days
Packaging Details :standard in carton box
Model :C120H
Pole(s) :1,2,3,4
Volt :1P,2P-220/230/240V, 3P,4P-380~415V
Hz :50~60Hz
Phase :1/3
Standard :EN/IEC60898, IEC60947
Breaking capacity :Ics=Icn=10000A
Thermal trip curve :C,D
Case material :Nylon PA6 recyclable
Wiring :terminal block, busbar duct etc. IP20B
Electric shock protection :Class II
Mechanical life :10,000
Electrical life :5,000
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Acti9 C120

CHINT Made In China

AC Use Miniature Circuit Breakers 63~125A,

Miniature Circuit Breakers for AC Current circuits, offering terminal distribution installation protection

C120H circuit breakers are multistandard circuit breakers that combine the following functions:
- Protection of cables against overloads and short-circuits in final distribution
- Manual control and isolation
- Earth leakage protection when combined with a Vigi C120 module without temperature derating: compliance with EN 61009
- Remote tripping, indication, by adding auxiliaries common to the entire C65 range.

  • Compliant with IEC60898-1, IEC60947-2
  • Available in 1P, 2P 3P, 4P
  • C, D tripping curve
  • Up to 500V AC.

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

General rules for choosing MCB
Technicala data of the network at the point considered:
The earthing systems(TNS,INC),Shrot-circuit current at the circuit-breaker installatino point,which must always be less than the breaking capacity of this device,Networl normal voltage.

DIN rail Miniature Circuit Breakers (MCB) offering circuit protection against short-circuit and overload currents. Suitable for isolation in compliance with IEC 60947

  • Features

Acti9 C120 DIN rail, miniature circuit breakers offer extensive features that provide maximum safety and continuity of service while minimizing service and intervention time:

  • Nominal current: 63 to 125 A
  • Large choice of breaking capacities and tripping curves (B, C, D)
  • Compliant with IEC EN 60898 or IEC 60947-2 depending on the version
  • Suitable for isolation: compliant with IEC 60947
  • VisiSafe provides a visible green indicator showing which circuits are disconnected and safe for maintenance operations
  • Operating voltage: up to 440 V AC
  • Insulation voltage: 500 V AC
  • IP20 terminal insulation
  • Optional add-on residual current device modules: Acti9 C120 Vigi
  • Optional electrical auxiliaries for remote Open/closed status or remote tripping of Acti9 C120 circuit breaker with shunt, overvoltage and undervoltage release.


Benefits

Longer product service life thanks to:

  • Good overvoltage withstand capacity: products are designed to offer a high industrial performance level (degree of pollution, rated impulse withstand voltage and insulation voltage)
  • High limitation performances
  • Fast closure independent of toggle operating speed.

Applications

  • Protection of electrical circuits in all industrial and commercial buildings
  • Particularly suited to higher ratings applications.

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

Acti9 C120 Industrial Circuit Breaker 63A~125A, 1P,2P,3P,4P for Circuit Protection AC230V/400V Home or Industrial Use

  Standard   IEC/EN 60947-2
Electrical features Rated current In A 63,80,100,125
Poles   1P,2P,3P,4P
Rated voltage Ue V 230/400
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity Ka 6~10
Rated impulse withstand voltage(1.2/50)Uimp V 6000
Dielectric test voltage at ind.Freq.for 1 min Kv 2.5
Pollution degree   3
Thermo-magnetic release characteristic   8-12In
Mechanical
features
Electrical life   1500(In=63A,80A,100A)
1000(In=125A)
Mechanical life   8000(In=63A,80A,100A)
7000(In=125A)
Contact position indicator   Yes
Pollution degree   IP20
Standard   IEC/EN 60947-2
Reference temperature for
setting of thermal element
30
Ambient temperature -5...+40(Special application please refer to P29 for temperature compensation correction)
Combination
with
sccssorles
(with daily average≦35℃)  
Storage temperation Terminal connection type -25..+70
  Cable/pin-type busbar
Terminal size top/bottom for cable mm2 50
AWG 18-1/0
Terminal size top/bottom for busbar mm2 50
AWG 18-1/0
Tightening torque N*m 3.5
In-Ibs. 3.1
Mounting   On DN rail EN 60715(35mm)by meas of fast clip device
Connection
Auxilary contact
  From top
Auxilary contact   Yes
Rated current
In (A)
Temperature compensation coefficient under various operational temperature
  -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 55℃ 60℃
63 1.28 1.21 1.14 1.07 1.00 0.84 0.87 0.85 0.82
80 1.22 1.16 1.11 1.05 1.00 0.95 0.91 0.88 0.86
100 1.22 1.18 1.11 1.05 1.00 0.95 0.91 0.88 0.88
125 1.22 1.16 1.11 1.05 1.00 0.95 0.91 0.88 0.86

Inquiry Cart 0